Most damaging transients arrive on the data line, not the power supply.

Coordinating Type 1, 2 and 3 devices — and the telecom entry path everyone forgets.

Most damaging transients arrive on the data line, not the power supply.
A strike terminates where the system lets it, not where the drawings say it should.

Surge protection gets specified on the incoming power supply almost by default — a Type 1 device at the main board, a Type 2 downstream, sometimes a Type 3 close to sensitive equipment. What gets missed, consistently, is the data and telecom entry point.

A nearby strike does not need to hit the building to cause damage. Induced transients travel on structured cabling, telephone lines and coaxial feeds just as readily as they do on the power supply — and in our experience, damaged routers, PABX equipment and access control panels are at least as common as damaged power supplies after a lightning event nearby.

Coordinating the chain

Surge protection only works as a coordinated chain — each stage of device has to let through a residual voltage low enough for the next stage to handle, all the way down to the equipment it is protecting. A Type 1 device at the main board with nothing downstream is a partial answer at best.

We assess the full entry path on every electrical audit: power, data and telecom — and size the SPD chain to the equipment actually connected, not just the incoming supply.

Not sure when your system was last measured?
We will test it, tell you what we find, and put the readings in writing.
Book an audit
Keep reading
Electrical 20 May 2026
“Can you do this?” is a licensing question before it is a technical one.
Standards 12 August 2026
Your LPS was compliant in 2009. That is not the same as compliant now.
Earthing 29 July 2026
One earth reading tells you nothing. A run of them tells you everything.